Technical Document
Specifications
Brand
ELCSeries
ALE
Type
Switched Mode
AC Input Voltage
190 V ac → 440V ac
Electrical Phase
1
AC or DC Input Voltage
ac
Number of Outputs
1
Input Voltage
230V → 440V ac
AC or DC Output Voltage
dc
Output Voltage
24V dc
Output Current
12.5A
Power Rating
300W
Dimensions
120 x 120 x 120mm
Depth
120mm
Width
120mm
Height
120mm
Minimum Temperature
+5°C
Model
DIN RAIL
Load Regulation
50mV
Special Features
Battery charger pb 24V, Low ripple <3mV
Mounting Type
DIN Rail Mount
Ripple And Noise
3mV
Output Voltage Adjustment Range
20 → 30V
Maximum Temperature
+45°C
Country of Origin
France
Product details
ALE2412 equipment power supply 300 W
Switch mode power supply 24 V, 12.5 A.
Output ripple < 3mV effective.
Complies with EN 61000-3-2, integrated ACTIVE power factor correction.
Diagnostic: relay status alert with changeover contact.
Adjustable output voltage 20 → 30 Volts.
15 A at 20 V - 10 A at 30 V.
Primary voltage 190 → 440 V.
Power: N+1 cumulative power supplies, thanks to active parallel capability.
Protection against short-circuits.
For mounting on DIN rail.
Standards
EN 60950, EN 50081-2, EN 61000-6-2
Stock information temporarily unavailable.
Please check again later.
130.860 OMR
Each (ex VAT)
137.403 OMR
Each (inc. VAT)
1
130.860 OMR
Each (ex VAT)
137.403 OMR
Each (inc. VAT)
1
Technical Document
Specifications
Brand
ELCSeries
ALE
Type
Switched Mode
AC Input Voltage
190 V ac → 440V ac
Electrical Phase
1
AC or DC Input Voltage
ac
Number of Outputs
1
Input Voltage
230V → 440V ac
AC or DC Output Voltage
dc
Output Voltage
24V dc
Output Current
12.5A
Power Rating
300W
Dimensions
120 x 120 x 120mm
Depth
120mm
Width
120mm
Height
120mm
Minimum Temperature
+5°C
Model
DIN RAIL
Load Regulation
50mV
Special Features
Battery charger pb 24V, Low ripple <3mV
Mounting Type
DIN Rail Mount
Ripple And Noise
3mV
Output Voltage Adjustment Range
20 → 30V
Maximum Temperature
+45°C
Country of Origin
France
Product details
ALE2412 equipment power supply 300 W
Switch mode power supply 24 V, 12.5 A.
Output ripple < 3mV effective.
Complies with EN 61000-3-2, integrated ACTIVE power factor correction.
Diagnostic: relay status alert with changeover contact.
Adjustable output voltage 20 → 30 Volts.
15 A at 20 V - 10 A at 30 V.
Primary voltage 190 → 440 V.
Power: N+1 cumulative power supplies, thanks to active parallel capability.
Protection against short-circuits.
For mounting on DIN rail.
Standards
EN 60950, EN 50081-2, EN 61000-6-2